Resumo
El objetivo principal de este estudio fue validar experimentalmente un modelo mecánistico para predecir la eficacia de enfriamiento (η) de placas
porosas construidas con arcilla expandida. El material de arcilla expandida fue físicamente caracterizado encontrando su masa específica, área
superficial y volumen. El modelo fue validado con datos de temperatura de bulbo seco (Tdb, ° C) y humedad relativa del aire (humedad relativa,%) que
fueron continuamente monitoreados en dos puntos diferentes, en contra y a favor de la dirección del aire que pasa a través de la placa porosa. La
recolección de datos se llevó a cabo de forma consecutiva durante un período de 10 días entre las 11:00 y 4:00 p.m. Los valores medios de η, simulados
y observados, fueron 74,8 ± 7,4% y 68,3 ± 8,3%, respectivamente. Basado en el modelo desarrollado, se observó que η fue mayor del 40% para Tdb>
30 ° C y HR constante en 45%. La simulación indicó que el aumento de la temperatura del aire puede afectar negativamente la producción en
invernaderos en Estados como Minas Gerais, Brazil, si no se revisan algunos criterios de diseño en el sistema de enfriamiento por evaporación.
Abstract
The main objective of this study was to experimentally validate a mechanistic model for predicting the cooling efficiency (η) of wetted porous plates
built with expanded clay. The expanded clay material was physically characterized by specific mass, surface area, and volume. The model was
validated with dry bulb temperature (Tdb, °C) and air relative humidity (RH, %) data, which were continuously monitored in two different points,
upstream and downstream the direction of the air passing through the porous plate. Data collection was carried out consecutively for a period of 10
days, between 11:00 a.m. and 4:00 p.m. Average values for η, simulated and observed, were 74.8 ± 7.4% and 68.3 ± 8.3%, respectively. Based on
the developed model, it was observed that η was higher than 40% for Tdb > 30 °C and constant RH at 45%. The simulation for predictions indicates
that the increase in the air temperature greater than 20 °C may affect negatively the production in greenhouses from states located in tropical and
subtropical countries as Minas Gerais, Brazil, if some design criteria in the evaporative cooling system are not revised.
Descrição
Área de concentração
Linha de pesquisa
Agência de desenvolvimento
Palavra chave
Marca
Objetivo
Procedência
Impacto da pesquisa
Resumen
ISBN
DOI
Citação
ALVES-DAMASCENO, F. et al. Assessment of evaporative cooling efficiency in greenhouses equiped with wetted porous plates. Dyna, [S.l.], v. 84, n. 203, p. 118-125, Dec. 2017.
Link externo
Avaliação
Revisão
Suplementado Por
Referenciado Por
Licença Creative Commons
Exceto quando indicado de outra forma, a licença deste item é descrita como acesso aberto