Please use this identifier to cite or link to this item: http://repositorio.ufla.br/jspui/handle/1/42431
Title: Real-time voltage sag detection and classification for power quality diagnostics
Keywords: Power quality
Voltage sag segmentation
Voltage sag classification
Distributed generation
Energia - Qualidade
Queda de tensão - Segmentação
Queda de tensão - Classificação
Geração distribuída de energia
Issue Date: Nov-2020
Publisher: Elsevier
Citation: NAGATA, E. A. et al. Real-time voltage sag detection and classification for power quality diagnostics. Measurement, [S. I.], v. 164, Nov. 2020. DOI: https://doi.org/10.1016/j.measurement.2020.108097
Abstract: This work proposes an innovative approach to detect, segment and classify voltage sags according to their causes. To detect and segment, Independent Component Analysis is used, with the advantage of being fast and with low computational effort in the operational stage, once it uses only 1/8 cycle of the fundamental component. For classification purposes, Higher-Order Statistics are used for feature extraction and the classifiers are based on Neural Networks and Support Vector Machines. It was tested signal windows of 1, 1/2, 1/4 and 1/8 cycle. For both detection/segmentation design and feature selection, it was used the metaheuristics Teaching-Learning-Based Optimization. Encouraging results were achieved for the simulated signals. In addition, real signals were used to evaluate the detection and segmentation method and good results were achieved in which a detection error rate of 0.86% was achieved.
URI: https://doi.org/10.1016/j.measurement.2020.108097
http://repositorio.ufla.br/jspui/handle/1/42431
Appears in Collections:DAT - Artigos publicados em periódicos
DEG - Artigos publicados em periódicos

Files in This Item:
There are no files associated with this item.


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.